    XGW-12~24kV Ring Cage(opening and closing)

    Updated on:2025-08-13

    Enquiry Hotline

    008618321814174
    • Product Details

    Cable Branch Box

    Model: XGW-12~24kV Ring Cage(opening and closing)

    Application:

    XGW-12~24KV ring net cage (opening and closing station) is a new generation of ring net switch equipment with modularization, multi-function, high reliability, compact structure and maintenance-free. It is suitable for ring net power supply or double radiation power supply of 10~35KV power supply lines, and can also be used for terminal power supply, which can control and protect electric energy in the power supply area. Widely used in urban ring network distribution with high power supply load density and cable-fed network, large factories, residential quarters and so on.

    XGW-12~24KV ring cage (opening and closing station) is mainly composed of SF6 gas insulated and closed compact switch gear (C-GIS) and metal (or nonmetal) outer box. All high-voltage live parts are enclosed in SF6 gas insulated stainless steel box, which can be freely combined according to the arrangement of incoming line unit, outgoing line unit, metering unit, contact unit and PT (power supply) unit according to user's needs, and can be loaded into power distribution automation system.

    In the ring network cabinet, only FTU/RTU and communication device are needed to communicate with the control center of the distribution automation system, and the voltage and current of the line can be varied.

    Measure the electric quantity and monitor the working state of each switch.

    Features:

    ● Ambient temperature: +45℃~-35℃, maximum temperature difference ≤25℃;

    ● Altitude: ≤4000m;

    ● Humidity: the daily average relative humidity is less than 95%; Daily average value of steam pressure < 2.2kPa; Average monthly relative humidity < 90%; Average monthly steam pressure < 1.8kPa;

    ● Seismic capacity: the seismic intensity shall not exceed 8 degrees;

    ● The surrounding air should be free from obvious pollution such as corrosive or combustible gas and water vapor;

    ● When the outdoor high pressure ring network cabinet is used beyond the normal use conditions, it needs to be negotiated with the manufacturer and reached an agreement.

    Specification:

    Item

    Unit

    Load Switch Unit

    Combined Electrical Apparatus Unit

    Circuit Breaker Unit


    Rated Voltage

    kV

    12/24




    Rated Frequency

    Hz

    50/60




    Main Bus Rated Current

    A

    630, 1250




    Rated Current

    A

    630

    125

    630, 1250


    Rated Short-Circuit Breaking Current

    kA/Cycles

    31.5

    20, 25/30



    Rated Short-Circuit Making Current (Peak)

    kA

    50

    80

    50, 63


    Rated Short-Time Withstand Current

    Main Circuit 4s / Grounding Circuit 4s

    kA

    25

    20, 25




    Grounding Connection Circuit 4s

    kA

    17.4

    17.4, 21.7



    Rated Peak Withstand Current

    Main Circuit / Grounding Circuit

    kA

    50

    50, 63




    Grounding Connection Circuit

    kA

    43.5

    43.5, 54.6



    Rated Transfer Current

    A

    1750 (12kV) / 1400 (24kV)





    Breaking and Making Capacity

    E3 Class

    E2 Class





    Rated Insulation Level

    Phase-to-Ground, Phase-to-Phase

    kV

    42 (12kV) / 65 (24kV)




    1min Power Frequency Withstand Voltage

    Vacuum Break, Isolation Break

    kV

    48 (12kV) / 79 (24kV)





    Phase-to-Ground, Phase-to-Phase

    kV

    75 (12kV) / 125 (24kV)





    Vacuum Break, Isolation Break

    kV

    85 (12kV) / 145 (24kV)




    SF6 Gas Rated Pressure (20°C relative value)

    Design Level and Rated Filling Level

    MPa

    0.04


    Minimum Functional Level


    0.02


    Pressure Relief Device Release Pressure


    0.14

    Protection Level

    Sealed Gas Compartment


    IP67


    Switchgear Enclosure


    IP4X

    Sealing Performance



    Annual Leakage Rate ≤ 0.01%