Product

Legend

It focuses on industrial automation control systems and related equipment solutions, and is deeply engaged in import and export trade

※ Your Current Location:Home - Product - 35kV Oil immersed power transformer
  • Transformer
  • Low-voltage switchgear assemblies
  • High-voltage switchgear assemblies
  • Cable branch box
  • Box-type substation
  • prev
    next

    35kV Oil immersed power transformer

    Updated on:2025-08-13

    Enquiry Hotline

    008618321814174
    • Product Details

    Transformer

    Model: 35kV Oil immersed power transformer

    Application:

    DC resistance test is the necessary test item for a transformer handover before delivery, it is the ideal equipment to measure DC resistance of transformer winding and high-power inductive devices. 

    This series of products is relatively advanced in design, and has been greatly improved  and improved in materials, structures and processes. The high and low pressure clamps  are tensioned by steel straps or upper beams and side beams to form  a  strong  frame  structure that enhances the core clamping force and the ability to withstand transport  shocks. It has strong anti-short circuit capability, beautiful appearance selection,reliable  operation, low loss and low noise,reaching the advanced level of similar foreign   products.

    Features:

    Executive standard

    GB  1094.1~2"General  Rules  for  Power  Transformers""The  Temperature  of  Oil-immersed Transformers" GB 1094.3"Insulation level,insulation test and external insulation air gap"

    GB 1094.5"The ability of power transformers to withstand short circuits"

    GB/T 6451"Technical parameters and requirements for oil-immersed power transformers" GB/T  15164 "Guidelines for Oil-immersed  Power Transformers"

    GB2536 "Transformer Oil"

    Specification:

    S1135KV oil immersed power transformer(50kVA~1600KVA three-phase double winding non-exciation voltage regulating distribution transformer)

    Rated

    Capacity (kVA)

    Voltage combination and tap range

    Junction group

    label

    Load loss

    (W)

    Load loss

    (W)

    No-load

    Current

    (%)

    Short circuit

    impedance

    (%)

    (H.V.)

    High voltage tap

    range(%)

     (L.V.)

    50

    35  38.5

    ±5

    ±2×2.5%

    0.4

    Dyn11 YynO

    130

    1200/1140

    1.30

    6.5

    100

    185

    2010/1910

    1.10

    6.5

    125

    215

    2370/2260

    1.10

    6.5

    160

    225

    2820/2680

    1.00

    6.5

    200

    270

    3320/3160

    1.00

    6.5

    250

    320

    3950/3760

    0.95

    6.5

    315

    385

    4750/4530

    0.95

    6.5

    400

    465

    5740/5470

    0.85

    6.5

    500

    545

    6910/6580

    0.85

    6.5

    630

    665

    7860

    0.65

    6.5

    800

    785

    9400

    0.65

    6.5

    1000

    920

    11500

    0.65

    6.5

    1250

    1120

    13900

    0.60

    6.5

    1600

    1350

    16600

    0.60

    6.5

    2000

    1590

    19700

    0.55

    6.5

    2500

    1890

    23200

    0.55

    6.5

    Note:1.For transformers with rated capacity of 500KVA and below,the load loss value above         the dagona line in the tables applicable to the Dyn11 comection group.

    2.according to user needs,can provide high voltage tapping range of±2×2.5%of the transformer.

    S1135KV oil immersed power transformer(630kVA~31500KVA three-phase double winding group non-excitation voltage regulating power transformer)

     Rated

    Capacity (kVA)

    Voltage combination and tap range

     Junction  group label

    Load loss

    (W)

    Load loss

    (W)

    No-load

    current

    (%)

    Short circuit impedance

    (%)

     (H.V.)

    High voltage tap

    range(%)

     (L.V.)

    8000

    35~38.5

    ±2×2.5%

    6.6

    1.05

    11

    Yd11

    7200

    38480

    0.42

    7.5

    10000

    8700

    45320

    0.42

    7.5

    12500

    10080

    53870

    0.40

    8.0

    16000

    12160

    65840

    0.40

    8.0

    20000

    14400

    79520

    0.40

    8.0

    25000

    17020

    94050

    0.32

    8.0

    31500

    20220

    112860

    0.32

    8.0

    Note 1:The external dimensions are designed according to the specific needs of the user.

    SZ1135KV  on-load  tap  change  oilimmersed  power  transformer(2000kVA-20000KVA  on-load  tap  change  power  transformer)

     Rated

    Capacity (kVA)

    Voltage combination and tap range

     Junction  group label

    Load loss

    (W)

    Load loss

    (W)

    No-load

    current

    (%)

    Short circuit impedance

    (%)

    (H.V.)

    High voltage tap

    range(%)

    (L.V.)

    2000

    35

    ±3×2.5

    6.310.5


    2300

    19240

    0.80

    6.5

    2500

    2720

    20640

    0.80

    6.5

    3150

    35~38.5

    ±3×2.5

    6.3 10.5

    Yd11

    3230

    24710

    0.72

    7.0

    4000

    3870

    29160

    0.72

    7.0

    5000

    4640

    34200

    0.68

    7.0

    6300

    5630

    36770

    0.68

    7.5

    8000


    7870

    40610

    0.60

    7.5

    10000

    9280

    48050

    0.60

    8.0

    12500

    35~38.5

    ±3×2.5

    6.3 6.6 10.5 11

    Ynd11

    10940

    56860

    0.56

    8.0

    16000

    13170

    70320

    0.54

    8.0

    20000

    15570

    82780

    0.54

    8.0